This protects your inverter from lightning strikes and over current. Please select the desired fuse size (in Amps).
The maximum open circuit Voltage is 600V for the surge protection. Please contact us if you require a higher rating.
Technical Advice to Installers.
According to solar industry standards for protection, two fuses are required, one for positive and one for the negative pole.
To calculate the fuse rating multiply the Amps of the PV string by x1.2.
Example PV String Amps 10.5A x 1.2 = 12.6 Amps. Nearest fuse 15A
Solar DC protection box 1 string
R1500,00R1450,00This protects your inverter from lightning strikes and over current. Please select the desired fuse size (in Amps).
3 in stock (can be backordered)
Description
This protects your inverter from lightning strikes and over current. Please select the desired fuse size (in Amps).
The maximum open circuit Voltage is 600V for the surge protection. Please contact us if you require a higher rating.
Technical Advice to Installers.
According to solar industry standards for protection, two fuses are required, one for positive and one for the negative pole.
To calculate the fuse rating multiply the Amps of the PV string by x1.2.
Example PV String Amps 10.5A x 1.2 = 12.6 Amps. Nearest fuse 15A